The Model LTN-3R UPS (550VA – 1.3kVA) is purpose-built for rugged outdoor applications where uninterrupted, conditioned power is critical. Unlike typical outdoor UPS units that offer only standby backup with minimal voltage regulation, the LTN-3R integrates a constant voltage transformer to deliver ±3% regulated, continuous sine wave output with magnetic isolation and full power conditioning. Its NEMA 3R rain-tight enclosure withstands harsh environments from -35°C to +55°C, while internal battery options provide runtimes from 30 minutes to 9.5 hours. Ideal for security, traffic control, telecom, and industrial sites, the LTN-3R ensures reliable performance in the most demanding outdoor environments.
Specifications
- Input Operating Voltage Range: +10%, -40% typical, load-dependent, without battery usage
- Input Frequency: 60 Hz, ±2.5 Hz
- Output Power Rating: kVA at 1.0 power factor (unity), kVA = kW
- Output Sine Wave Voltage: Maximum 3% harmonic distortion, any single harmonic
- Voltage Regulation: ±3% typical
- Isolation: Galvanic
- Operating Temperature: -35°C to +55°C (-31°F to 131°F)
- Total System MTBF: 100,000 hours
- Common Mode Noise Attenuation: 120 dB
- Transverse Mode Noise Attenuation: 70 dB
- Efficiency: 89% typical
- Single Phase Sizes: 550 VA, 1 kVA, 1.3 kVA