The Model LTN UPS (700VA – 2.1kVA) is a rugged, single-phase industrial power system designed to provide continuous, regulated, computer-grade power in harsh environments. Unlike many “industrial” systems that are simply commercial units in an enclosure, the LTN delivers true power conditioning with a constant voltage transformer for ±3% regulation, galvanic isolation, and noise filtering. Its NEMA 2 drip-proof design ensures durability, while internal batteries offer 30 minutes to 7 hours of runtime at full load. Ideal for SCADA, process control, security, telecom, and broadcast systems, the LTN ensures uninterrupted operation, equipment protection, and dependable performance.
Specifications
- Input Operating Voltage Range: +10%, -40% typical, load-dependent, without battery usage
- Input Frequency: 60 Hz, ±2.5 Hz
- Output Sine Wave Voltage: Maximum 3% harmonic distortion, any single harmonic
- Voltage Regulation: ±3% typical
- Isolation: Galvanic
- Operating Temperature: 0°C to 40°C (32°F to 104°F)
- Total System MTBF: 100,000 hours
- Common Mode Noise Attenuation: 120 dB
- Transverse Mode Noise Attenuation: 70 dB
- Efficiency: 89% typical
- Single Phase Sizes: 700VA, 850VA, 1.0kVA, 1.2kVA, 1.4kVA, 1.6kVA, 1.8kVA, 2.1kVA