MV-AutoVAR specifications
Voltage | 2,300 to 14,400 V |
Certifications | ANSI
IEEE NEC NESC CSA (when specified) |
Detuned filters | Standard filters detuned to 4.2, 4.4, 4.6 or 4.7 |
Lightning arresters | Standard distribution heavy duty class, optional intermediate or station class |
Vacuum switch | 15 kV, oil or solid dielectric
Certified to ANSI C37.66 |
Heavy-duty capacitor units | 125% continuous rms overvoltage capability, 15,000 A fault handling capability, 100 kA transient current withstand capability, 131 ºF (55ºC) ambient temperature operation, and 135% peak overvoltage capability |
Communications gateway | Integrated Eaton Power Xpert Gateway allows remote monitoring of the Type CM controller via ethernet |