The ULTRA-K Series 600K-he Single Phase (5 kVA – 25 kVA ) is a high-efficiency, K-rated power conditioning transformer engineered to protect sensitive electronic loads while lowering operating costs. Designed to exceed DOE 2016 minimum efficiency standards, it delivers superior electrical noise attenuation and transient voltage suppression, ensuring clean, reliable power for mission-critical systems. With multiple K-factor ratings (K4, K7, K13, K20), the ULTRA-K safely handles harmonic currents from non-linear loads, extending the life of LED drivers, ballasts, and electronic equipment. Durable copper-wound construction, optional surge protection, and versatile enclosure choices make it a long-lasting, adaptable solution for industrial and commercial applications.
Specifications
- Efficiency: Meets and exceeds DOE 2016 minimum efficiency standards (U.S. DOE 10 CFR Part 431). Meets and exceeds CSA Standard C802.2-12 (Canada).
- Voltage Compensation Taps: Full capacity above and below nominal with multiple field-selectable taps.
- Output Impedance: 2% – 3.5% typical.
- Output Distortion: Less than 1.0% THD added under linear load.
- Load Regulation: 2% typical, no load to full load.
- Overload Capacity: Up to 500% for 10 seconds, 1000% for 1 cycle.
- Isolated Neutral: Establishes a new neutral-to-ground bond on the transformer’s output for safer operation.
- Common Mode Noise Attenuation: 126 dB (standard double shielding); 146 dB (optional triple shielding).
- Transverse Mode Noise Attenuation: 3 dB down at 10 kHz, decaying 20 dB per decade; decaying 40 dB with optional SPD & filter.
- Operating Temperature: -25°C to +40°C
- Audible Noise: 45 – 50 dBA at 1 meter (size dependent).
- Temperature Rise: 135°C rise above ambient under non-linear loading, per UL 1561 standard.
- Certifications: UL 1561 Listed and labeled for operation at or below specified K-factor rating. C-UL Listed to CSA C22.2 No. 47-13.
- Single Phase Sizes: 5 kVA, 8 kVA, 10 kVA, 15 kVA, 20 kVA, 25 kVA