Harmonic correction unit specifications
HCUn series
Power electronics | 3-level IGBT |
Control topology | Digital harmonic FFT Digital instantaneous reactive power |
Efficiency and losses | 208 Vac ≥ 95% Three-phase compensation: ≤ 17.7 W/A Three-phase + N compensation: ≤ 19.7 W/A 380–415 Vac ≥ 97% Three-phase compensation: ≤ 20.4 W/A Three-phase + N compensation: ≤ 22.6 W/A |
Current transformer | Any ratio with 1 A or 5 A secondary; Class 1.0 accuracy; 50/60 or 400 Hz rated (instrument rated or better); Grounded; can be shared with other devices |
CT VA loading | 1 A: 0.04 VA 5 A: 1 VA |
Quantity of CT | Two or three CTs for three-phase loads; three CTs are required for four-wire with neutral connected loads CT position (Grid or load sense) |
Control basis | Closed or open loop |
Modes or Operation | Multi-modes simultaneously or discrete |
Spectrum cancellation and selection | 2nd to 51st harmonic order; discrete, fully selectable adjustable per harmonic order (amplitude % and ON/OFF) Phase harmonic correction Neutral harmonic correction with user-adjustable current limit up to three times unit rating Power factor correction (cos) Mains current load balancing |
Operational features | % THDi setpoint, % THDv setpoint, Target PF setpoint |
Harmonic attenuation and filtering performance | THDi < 3% in closed loop control; maximum 20:1 THDi (typical reduction with load harmonic above 50% unit rating) requires 3% or higher inductive impedance per nonlinear load |
Mains current load balancing | Negative and zero sequence; selectable individually or simultaneously |
Power factor correction | Optimize PF and target PF (cos) programmable leading (capacitive) or lagging (inductive) |
Resonance avoidance | Output at specific harmonic order turned off if resonance or lack of impedance detected or manually turned off |
HCU2 series
Standard rms output current ratings | 380 Vac to 480 Vac: 60 A, 120 A, 200 A, 300 A
600 Vac: 47 A, 94 A, 157 A, 235 A 690 Vac: 40 A, 80 A, 133 A, 200 A |
Nominal frequency | 50/60 Hz, +/- 3 Hz auto sensing |
Number of phases | 3-phase |
Topology | Digital harmonic FFT
Digital reactive power |
Losses | to 480 Vac <3%
to 690 Vac <5% |
CT VA loading | 1.0 VA (5 A CT secondary) |
Spectrum cancellation | 2nd to 51st, discrete; fully selectable per harmonic order (amplitude and on/off) |
Control basis | Closed loop (for new installations)
Open loop compatible for retrofit applications |
Harmonic attenuation | Closed loop: <3% THD(i); max 20:1 THD)i) reduction with load harmonic current above 50% of HCU2 rating
Open loop: <5% TDD Required 3% or higher inductive impedance per nonlinear load |
Harmonic operational features | % THDi set point
% THDv set point |
Harmonic avoidance | Output at specific harmonic order turned off if resonance or lack-of impedance detected; or manually turned off |
Parallal operation | Up to 10 units per set of CT (to 51st order), any size combination
Backward compatibility with Eaton HCUE operated in parallel Contact Eaton for applications of more than 10 units |
Parallel operation options | Master/master
Master/slave Multi-master/multi-slave Same as Eaton HCUE for retrofits |
Parallel sequence options | Lead/lag with unit rotation: one unit operates to full capacity before next unit turns on; times rotation
Load share: all operating units function at the same output percentage |
Parallel HMI control | Any unit permits viewing and changing parameter settings of complete system or any other unit in parallel system |
Parallel communications | Proprietary COM bus between operating units |
Power factor correction | Optimized unity PF, leading (capacitive) or lagging (inductive) power factor (Cos f) to target |
Control response time | 25 µs |
Harmonic correction time | 2 cycles |
Reactive correction time | 1/4 cycle |
Display | 144 mm QVGA TFT 64k-color touchscreen |
Display parameters | Hundreds of parameters are available. Examples include: THDi, THDv, oscilloscope for viewing many selected parameters, phasor diagrams, load power, measured currents for Ih, Is, If, I neg seq, PF (Cos f), injected currents for Ih, I reactive, I neg seq, etc. |
Communications capability | Modbus RTU, Modbus TCP/IP |
Discrete input/outputs | 4 input and 4 output dry contracts; assignable |
Noise level (ISO3746) | <70 dB at 1 meter from unit surface |
Earthing (grounding) systems | EMC filter ground switch for Isolated Terra, high resistance ground or corner grounded systems |